We appreciate your interest in part number CD3-A3-DU-0100-01A, which is currently available for purchase here on Jet Force Aero. For your reference, this item is produced by Eaton Corporation and is listed with the NSN 5925-01-175-8203, as well as the description “Circuitbreaker.” If this matches your requirements, we encourage you to fill out the Request for Quote (RFQ) form featured on this page to receive tailored purchasing options on part number CD3-A3-DU-0100-01A. All that we ask is that you submit as many details about your procurement needs as possible, such as your desired quantity, budget, and anticipated fulfillment timeframe, as this will enable our specialists to craft an ideal response for you.
Note : We Will Not Share Your Information With Any Third Parties.
In addition to part number CD3-A3-DU-0100-01A, be sure to explore our website further for related items produced by Eaton Corporation under the CAGE Code 1W134 as you wish. We also feature catalogs to help you find additional options that are categorized under FSC 5925 Circuit Breakers and the NSN 5925-01-175-8203. Regardless of which NSN parts you need from us, rest assured that we will always treat you to affordable solutions where you never have to sacrifice quality or prompt fulfillment. We are ready to assist you with all your sourcing needs, so kick off quotation at your convenience.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-01-175-8203 Item PartTypeName: CIRCUIT BREAKER | 5925 | 011758203 | 0 | P | ||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | A | |||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| CD3-A3-DU-0100-01A | 5 | 2 | 5 |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| ABTD | MOUNTING SLOT WIDTH | 0.164 INCHES NOMINAL |
| ADAQ | BODY LENGTH | 5.768 INCHES MINIMUM AND 5.832 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 3.046 INCHES MINIMUM AND 3.110 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.515 INCHES MINIMUM AND 3.579 INCHES MAXIMUM |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.994 INCHES MINIMUM AND 1.058 INCHES MAXIMUM |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.718 INCHES MINIMUM AND 2.782 INCHES MAXIMUM |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.994 INCHES MINIMUM AND 1.058 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AGAV | END ITEM IDENTIFICATION | DEFENSE SUPPORT PROGRAM |
| AJEC | BOSS HEIGHT | 0.187 INCHES MINIMUM AND 0.251 INCHES MAXIMUM |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.172 INCHES MINIMUM AND 3.296 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 3 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE AND 6 SLOT |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE,TWO,AND THREE LINKED |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 35.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| CWJK | CASE MATERIAL | PLASTIC |
| FEAT | SPECIAL FEATURES | ITEM IS UL LISTED; CHECK VALVE IS FURNISHED AS STANDARD FOR THIS CIRCUIT BREAKER |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |